33942647 (021)

HDW320S163FHNN56M

air circuit breaker, HDW3, 2000AF, 1600 A, 3P, fixed horizontal, 6 NO + 6 NC

توضیحات تکمیلی

Range of product

HDW3

Product or component type

Air circuit breaker

Frame size

2000AF

[Icu] Ultimate breaking capacity

65kA at 400 V load
40kA at 690 V load

[Ics] Rated service breaking capacity

65kA at 400 V
40kA at 690 V

[Icw] Rated short-time withstand current

65kA at 400 V duration: 1s
40kA at 690 V duration: 1s

[In] Rated current

1600A

Poles description

3P

Mounting mode

Fixed

Mounting position

Horizontal

[Uc] Control circuit voltage

230V AC: motor mechanism (MCH) + closing release (XF)
230V AC: shunt release (MX)

Voltage release type

Without undervoltage release

Maximum tripping time

25ms

Maximum closing response time

70ms

Auxiliary contact composition

6NO + 6NC

Product compatibility

Series intelligent controller iTR326A standard protection

Width

397mm

Height

364mm

Depth

327mm

Net weight

41.4kg